File: //lib/netdata/conf.d/health.d/apcupsd.conf
# you can disable an alarm notification by setting the 'to' line to: silent
template: apcupsd_ups_load_capacity
on: apcupsd.ups_load_capacity_utilization
class: Utilization
type: Power Supply
component: UPS device
lookup: average -10m unaligned of load
units: %
every: 1m
warn: $this > (($status >= $WARNING) ? (70) : (80))
delay: down 10m multiplier 1.5 max 1h
summary: APC UPS load
info: APC UPS average load over the last 10 minutes
to: sitemgr
template: apcupsd_ups_battery_charge
on: apcupsd.ups_battery_charge
class: Errors
type: Power Supply
component: UPS device
lookup: average -60s unaligned of charge
units: %
every: 60s
warn: $this < 100
crit: $this < 40
delay: down 10m multiplier 1.5 max 1h
summary: APC UPS battery charge
info: APC UPS average battery charge over the last minute
to: sitemgr
template: apcupsd_last_collected_secs
on: apcupsd.ups_status
class: Latency
type: Power Supply
component: UPS device
calc: $now - $last_collected_t
every: 10s
units: seconds ago
warn: $this > (($status >= $WARNING) ? ($update_every) : ( 5 * $update_every))
delay: down 5m multiplier 1.5 max 1h
summary: APC UPS last collection
info: APC UPS number of seconds since the last successful data collection
to: sitemgr
#Send out a warning when SELFTEST code is BT or NG. Code descriptions can be found at:
#http://www.apcupsd.org/manual/#:~:text=or%20N/A.-,SELFTEST,-The%20results%20of
template: apcupsd_ups_selftest_warning
on: apcupsd.ups_selftest
lookup: max -1s unaligned match-names of BT,NG
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS self-test failed due to insufficient battery capacity or due to overload
to: sitemgr
#Send out a warning when STATUS code is ONBATT,OVERLOAD,LOWBATT,REPLACEBATT,NOBATT,COMMLOST
#https://man.archlinux.org/man/apcaccess.8.en#:~:text=apcupsd%20was%20started-,STATUS,-%3A%20UPS%20status.%20One
template: apcupsd_ups_status_onbatt
on: apcupsd.ups_status
lookup: max -1s unaligned match-names of ONBATT
units: status
every: 10s
warn: $this == 1
delay: up 1m down 15m multiplier 1.5 max 1h
info: APC UPS has switched to battery power because the input power has failed
to: sitemgr
template: apcupsd_ups_status_overload
on: apcupsd.ups_status
lookup: max -1s unaligned match-names of OVERLOAD
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS is overloaded and cannot supply enough power to the load
to: sitemgr
template: apcupsd_ups_status_lowbatt
on: apcupsd.ups_status
lookup: max -1s unaligned match-names of LOWBATT
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS battery is low and needs to be recharged
to: sitemgr
template: apcupsd_ups_status_replacebatt
on: apcupsd.ups_status
lookup: max -1s unaligned match-names of REPLACEBATT
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS battery has reached the end of its lifespan and needs to be replaced
to: sitemgr
template: apcupsd_ups_status_nobatt
on: apcupsd.ups_status
lookup: max -1s unaligned match-names of NOBATT
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS has no battery
to: sitemgr
template: apcupsd_ups_status_commlost
on: apcupsd.ups_status
lookup: max -1s unaligned match-names of COMMLOST
units: status
every: 10s
warn: $this == 1
delay: up 0 down 15m multiplier 1.5 max 1h
info: APC UPS communication link is lost
to: sitemgr