File: //lib/netdata/conf.d/go.d/snmp.profiles/default/_std-ups-mib.yaml
metric_tags:
- OID: 1.3.6.1.2.1.33.1.1.1
symbol: upsIdentManufacturer
tag: ups_ident_manufacturer
- OID: 1.3.6.1.2.1.33.1.1.2
symbol: upsIdentModel
tag: ups_ident_model
- OID: 1.3.6.1.2.1.33.1.1.5
symbol: upsIdentName
tag: ups_ident_name
metrics:
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.1.0
name: upsBatteryStatus
chart_meta:
family: 'Hardware/Battery/Status'
description: The indication of the capacity remaining in the UPS system's batteries
unit: "{status}"
mapping:
1: unknown
2: batteryNormal
3: batteryLow
4: batteryDepleted
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.2.0
name: upsSecondsOnBattery
chart_meta:
family: 'System/Battery/Runtime/OnBattery'
description: If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power
unit: "s"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.3.0
name: upsEstimatedMinutesRemaining
chart_meta:
family: 'System/Battery/Runtime/Remaining'
description: An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off
unit: "min"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.4.0
name: upsEstimatedChargeRemaining
chart_meta:
family: 'System/Battery/Charge/Remaining'
description: An estimate of the battery charge remaining expressed as a percent of full charge
unit: "%"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.5.0
name: upsBatteryVoltage
chart_meta:
family: 'Hardware/Battery/Voltage/Value'
description: The magnitude of the present battery voltage
unit: "V"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.6.0
name: upsBatteryCurrent
chart_meta:
family: 'Hardware/Battery/Current/Value'
description: The present battery current
unit: "A"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.2.7.0
name: upsBatteryTemperature
chart_meta:
family: 'Hardware/Battery/Temperature/Value'
description: The ambient temperature at or near the UPS Battery casing
unit: "Cel"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.3.1.0
name: upsInputLineBads
chart_meta:
family: 'PowerFlow/Input/Error/OutOfTolerance'
description: A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance
unit: "{transition}"
metric_type: monotonic_count
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.3.2.0
name: upsInputNumLines
chart_meta:
family: 'PowerFlow/Input/Line/Count'
description: The number of input lines utilized in this device. This variable indicates the number of rows in the input table
unit: "{line}"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.4.1.0
name: upsOutputSource
chart_meta:
family: 'PowerFlow/Output/Source/Status'
description: The present source of output power
unit: "{status}"
mapping:
1: other
2: none
3: normal
4: bypass
5: battery
6: booster
7: reducer
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.4.2.0
name: upsOutputFrequency
chart_meta:
family: 'PowerFlow/Output/Frequency/Value'
description: The present output frequency
unit: "Hz"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.4.3.0
name: upsOutputNumLines
chart_meta:
family: 'PowerFlow/Output/Line/Count'
description: The number of output lines utilized in this device. This variable indicates the number of rows in the output table
unit: "{line}"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.5.1.0
name: upsBypassFrequency
chart_meta:
family: 'PowerFlow/Bypass/Frequency/Value'
description: The present bypass frequency
unit: "Hz"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.5.2.0
name: upsBypassNumLines
chart_meta:
family: 'PowerFlow/Bypass/Line/Count'
description: The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table
unit: "{line}"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.6.1.0
name: upsAlarmsPresent
chart_meta:
family: 'System/Alarm/Active'
description: The present number of active alarm conditions
unit: "{alarm}"
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.7.3.0
name: upsTestResultsSummary
chart_meta:
family: 'System/Test/Result/Status'
description: The results of the current or last UPS diagnostics test performed
unit: "{status}"
mapping:
1: donePass
2: doneWarning
3: doneError
4: aborted
5: inProgress
6: noTestsInitiated
- MIB: UPS-MIB
symbol:
OID: 1.3.6.1.2.1.33.1.7.5.0
name: upsTestStartTime
chart_meta:
family: 'System/Test/StartTime/Value'
description: The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated
unit: "s"
- MIB: UPS-MIB
table:
OID: 1.3.6.1.2.1.33.1.4.4
name: upsOutputTable
symbols:
- OID: 1.3.6.1.2.1.33.1.4.4.1.2
name: upsOutputVoltage
chart_meta:
family: 'PowerFlow/Output/Voltage/Value'
description: The present output voltage
unit: "V"
- OID: 1.3.6.1.2.1.33.1.4.4.1.3
name: upsOutputCurrent
chart_meta:
family: 'PowerFlow/Output/Current/Value'
description: The present output current
unit: "A"
- OID: 1.3.6.1.2.1.33.1.4.4.1.4
name: upsOutputPower
chart_meta:
family: 'PowerFlow/Output/Power/Active'
description: The present output true power
unit: "W"
- OID: 1.3.6.1.2.1.33.1.4.4.1.5
name: upsOutputPercentLoad
chart_meta:
family: 'PowerFlow/Output/Load/Usage'
description: The percentage of the UPS power capacity presently being used on this output line
unit: "%"
metric_tags:
- symbol:
OID: 1.3.6.1.2.1.33.1.4.4.1.1
name: upsOutputLineIndex
tag: ups_output_line_index
- MIB: UPS-MIB
table:
OID: 1.3.6.1.2.1.33.1.3.3
name: upsInputTable
symbols:
- OID: 1.3.6.1.2.1.33.1.3.3.1.2
name: upsInputFrequency
chart_meta:
family: 'PowerFlow/Input/Frequency/Value'
description: The present input frequency
unit: "Hz"
- OID: 1.3.6.1.2.1.33.1.3.3.1.3
name: upsInputVoltage
chart_meta:
family: 'PowerFlow/Input/Voltage/Value'
description: The magnitude of the present input voltage
unit: "V"
- OID: 1.3.6.1.2.1.33.1.3.3.1.4
name: upsInputCurrent
chart_meta:
family: 'PowerFlow/Input/Current/Value'
description: The magnitude of the present input current
unit: "A"
- OID: 1.3.6.1.2.1.33.1.3.3.1.5
name: upsInputTruePower
chart_meta:
family: 'PowerFlow/Input/Power/Active'
description: The magnitude of the present input true power
unit: "W"
metric_tags:
- symbol:
OID: 1.3.6.1.2.1.33.1.3.3.1.1
name: upsInputLineIndex
tag: ups_input_line_index
- MIB: UPS-MIB
table:
OID: 1.3.6.1.2.1.33.1.5.3
name: upsBypassTable
symbols:
- OID: 1.3.6.1.2.1.33.1.5.3.1.2
name: upsBypassVoltage
chart_meta:
family: 'PowerFlow/Bypass/Voltage/Value'
description: The present bypass voltage
unit: "V"
- OID: 1.3.6.1.2.1.33.1.5.3.1.3
name: upsBypassCurrent
chart_meta:
family: 'PowerFlow/Bypass/Current/Value'
description: The present bypass current
unit: "A"
- OID: 1.3.6.1.2.1.33.1.5.3.1.4
name: upsBypassPower
chart_meta:
family: 'PowerFlow/Bypass/Power/Active'
description: The present true power conveyed by the bypass
unit: "W"
metric_tags:
- symbol:
OID: 1.3.6.1.2.1.33.1.5.3.1.1
name: upsBypassLineIndex
tag: ups_bypass_line_index
- MIB: UPS-MIB
table:
OID: 1.3.6.1.2.1.33.1.6.2
name: upsAlarmTable
symbols:
- OID: 1.3.6.1.2.1.33.1.6.2.1.3
name: upsAlarmTime
chart_meta:
family: 'System/Alarm/Time/Value'
description: The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0
unit: "s"
metric_tags:
- tag: ups_alarm_descr
symbol:
OID: 1.3.6.1.2.1.33.1.6.2.1.2
name: upsAlarmDescr